Raypak Protege VSP Pumps
Raypak publishes more of this interface than any other manufacturer here: protocol, baud rate, slave address, function codes, cable type and length are all in the manual. It makes the Protege the least ambiguous pump on the pad to integrate.
The published specification
| Item | Value |
|---|---|
| Protocol | Modbus RTU |
| Max baud rate | 9600 bps |
| Selectable baud rates | 1200, 2400, 4800, 9600 |
| Function codes | 0x03, 0x04, 0x06, 0x16 |
| Slave address range | 1 to 247, default 2 |
| Bus | Isolated A/B, no 120 ohm terminating resistor fitted |
| Connector | SP1310, four pin |
Wiring the SP1310 connector
The RS-485 socket is on the side of the variable-speed drive. Raypak supplies the connector but not a cable, so you make the lead up yourself. Pin numbers are moulded into the base of the terminals.
| Pin | Function | iSmart Module |
|---|---|---|
| 1 | A | PORT terminal A |
| 2 | B | PORT terminal B |
| 4 | Ground and 120 ohm termination, long runs only | See below |
- 1
Disassemble the female connector
Pin numbers are on the base of the terminals — check them rather than counting.
- 2
Prepare the cable
Raypak specifies 2-wire 22 AWG unshielded twisted pair, up to 100 m (109 yards) between pump and controller.
- 3
Solder pin 1 to A and pin 2 to B
Then reassemble the connector and plug it into the RS-485 socket on the pump.
- 4
Set the baud rate at the pump
Use the pump's baud rate menu to pick 1200, 2400, 4800 or 9600, then press MODE to save. It must match what the module is configured for.
When it does not respond
| Symptom | Where to look first |
|---|---|
| No communication at all | Baud rate mismatch, then the slave address — remember the default is 2. |
| Still nothing | Swap A and B, then confirm the connector is in the RS-485 socket and not an adjacent one. |
| Works close, fails on a long run | Missing termination. Bring pin 4 in with ground and a 120 ohm resistor. |
| Intermittent | Run exceeds 100 m, or the pair is not twisted. |
Sources
- Raypak, Protege Variable Speed Pump Installation & Operation Manual (241832) — RS-485 specifications, SP1310 pin assignment, cable requirements and the baud rate menu
- iSmart Module relay driver board — KiCad schematic and BOM. PORT A-D are an unbuffered RS-485 pass-through carrying A, B and G, with no termination fitted