Pentair UltraTemp Heat Pump
UltraTemp offers relay control on its three-wire remote terminals or RS-485 on a separate connector. Whichever you wire, there is a Remote Mode setting on the panel that has to agree with it, and the heat pump ignores the wiring until it does.
Two connectors, two methods
| Connector | Method | Remote Mode setting |
|---|---|---|
| J7 | Three-wire remote terminals, dry contacts | RELAY |
| J8 | RS-485 serial connection | RS-485 |
Relay mode on J7
J7 is the three-wire remote terminal block. It works the way a pool and spa remote does: a common plus two selects, one calling for pool heating and one for spa. Drive each select from a dry contact on the module using COM and N.O so both rest open and the heat pump idles.
RS-485 on J8
J8 is the RS-485 connector. It follows the same Pentair colour convention as the pumps and the MasterTemp.
| Pin | Colour | Signal | iSmart Module |
|---|---|---|---|
| 2 | Green | DATA- | PORT terminal B |
| 3 | Yellow | DATA+ | PORT terminal A |
When it does not respond
| Symptom | Where to look first |
|---|---|
| No response to anything | Remote Mode still set to OFF. Check this before the wiring. |
| Wired to J8 but silent | Remote Mode set to RELAY, or green and yellow swapped. |
| Contacts close but nothing happens | Remote Mode set to RS-485 while wired to J7. |
| Starts late every time | Compressor restart delay, which is normal. |
| Runs but never reaches setpoint | Ambient conditions and water flow, not the control link. |
Sources
- Pentair, UltraTemp Heat Pump Installation and User's Guide — J7 three-wire remote terminals, J8 RS-485 connector pin colours and the Remote Mode menu
- iSmart Module relay driver board — KiCad schematic and BOM. H1/H2 and AUX1/AUX2 are optocoupled dry relay contacts (N.C / COM / N.O); PORT A-D are an unbuffered RS-485 pass-through