Blue Torrent Variable Speed Pumps
Read this one before quoting a job. Blue Torrent's own manuals describe no external control interface of any kind, and the RS-485 people find on these pumps is not a control port — it is the pump's internal keypad bus.
What the manuals actually document
Blue Torrent publishes installation and operation manuals for their in-ground variable-speed range. Across both of them there is no mention of RS-485, Modbus, digital inputs, dry contacts, an automation system or an external control interface. Not a missing diagram — the capability is not described at all.
| Feature | Detail |
|---|---|
| Onboard schedule | Four speeds, SPEED 1 highest priority through SPEED 4 lowest |
| Schedule limit | 24 hours total; raising one speed's duration takes it from lower-priority speeds |
| Freeze protection | On by default, 1000 RPM default, settable 750-3450 RPM, trigger 40-50 F |
| Supply | 230 V single phase, permanent connection, dedicated circuit |
| External control | None documented |
The RS-485 people find is the keypad bus
That is a different proposition from every other pump in this documentation. On a Pentair, Jandy, Raypak or Nidec the manufacturer publishes an interface, names the terminals and expects a controller on the other end. Here there is no published interface, so anything on that connector is undocumented behaviour that Blue Torrent has not committed to.
- The protocol is not published, so it can only be reverse-engineered.
- Nothing obliges Blue Torrent to keep it stable between production runs, and these pumps are built on a platform sold under several brand names.
- Occupying the keypad's connector risks E-16 faults and leaves the customer without a working local display.
- Opening the drive to reach it is very likely a warranty question, and the drive carries residual voltage for five minutes after isolation.
The method Blue Torrent does sanction
The manual states the pump should be permanently connected to a circuit breaker, a two-pole timer, or a two-pole relay. That last option is the supported route to external control: switch the pump's supply and let its own schedule decide speed.
- Drive a two-pole contactor from H1, H2, AUX1 or AUX2 using COM and N.O so the pump rests off.
- Do not switch the pump's mains load through the module's relay directly — use a contactor rated for the pump and let the module's dry contact operate its coil.
- The pump must stay on a dedicated circuit with no other loads, and a dedicated GFCI breaker if GFCI protected.
A lead worth following up
What to tell a customer
| They ask | Honest answer |
|---|---|
| Can the app control my Blue Torrent's speed? | Not through anything the manufacturer supports. Speeds are set on the pump. |
| Can the app turn it on and off? | Yes, by switching its supply through a contactor — with freeze protection moved to the module. |
| I saw someone do it with RS-485 online | That is the pump's internal display bus, not a control port. It works until it does not, and it is not something to build a warranty around. |
| Should I change the pump? | If full speed control matters, a pump with a published interface will cost less in the long run than working around one without. |