Nidec

Nidec Neptune 1.65 / 2.25 / 2.7 THP Pumps

The Neptune is one of the better-documented motors on the pad: clearly labelled Modbus and switch-input terminal blocks, and a +12 V source to drive the inputs. The catch is that Nidec does not publish the protocol — you have to ask them for it.

Two ways in

Modbus (TB3)Switch inputs (TB4)
ConductorsThree — A, B and groundOne per input, plus a source and ground
SignalRS-485 differentialSwitch closure carrying +12 V
Module outputPORT A or PORT BUp to four dry contacts
ControlFull speed controlFour fixed steps at 25% increments
PriorityOverrides the motor's own UIINP #4 highest, UI lowest

Modbus on TB3

TerminalFunctioniSmart Module
TB3-1GND (Modbus)PORT terminal G
TB3-2A (Modbus)PORT terminal A
TB3-3B (Modbus)PORT terminal B
TB3-4No connectLeave empty
Nidec labels these terminals explicitly, which removes the usual guesswork. TB3-4 is deliberately unused.
The Neptune's two control terminal blocks: TB3 carrying Modbus ground, A and B, and TB4 carrying +12 V, four discrete inputs and ground.
Two blocks, two methods. TB3 is a three-wire Modbus connection; TB4 needs the +12 V on pin 1 switched into an input.

Discrete switch inputs on TB4

The fallback is four switch inputs that run the motor at fixed steps. Unlike the Century motors, these do not need a supply of your own: TB4-1 provides +12 V, and a dry contact switches it into whichever input you want. An external DC supply can be used instead, in which case its ground must be tied to the TB4-6 ground terminal.

TerminalFunction
TB4-1+12 V source
TB4-2INP #1
TB4-3INP #2
TB4-4INP #3
TB4-5INP #4
TB4-6GND
InputStepRPM at default limitsPriority
INP #4100%3450Highest
INP #375%2730
INP #250%2011
INP #125%1291Lowest
Speeds are 25% increments of the standard range. The RPM figures assume the default 600 minimum and 3450 maximum — change either and every figure moves.

Priority runs from INP #4 downward, with the motor's own user interface lowest. Drive one input at a time and treat the hierarchy as a safety net rather than a control strategy.

The auxiliary load relay

The Neptune has an optional auxiliary load relay that closes automatically at 2100 RPM, intended to enable equipment that depends on flow — a chlorine generator, a heater or a cleaner. It is worth knowing about even if you do not use it, because it may already be doing some of the interlocking on an existing installation.

The DIP switch is voltage selection only

When it does not respond

SymptomWhere to look first
No Modbus communicationSwap A and B, then confirm Remote Control is enabled at the motor's UI.
Motor ignores the bus and runs a fixed speedA switch input is asserted. INP #4 down to INP #1 all outrank the bus.
Nothing happens when a contact closesThe input needs +12 V through it. Confirm TB4-1 is landed, or that an external supply has its ground tied to TB4-6.
Comm-lost faults after a period of runningCheck the connections at the drive interface board and the run back to the controller; the manual treats these as wiring faults first.
Speeds do not match the tableThe motor's minimum or maximum RPM has been changed from the defaults.

Sources