MOOV

Moov AI Pumps

Electrically the AI is the same as the VSP — one seven-pin connector, four digital inputs, a Modbus pair. What differs is the behaviour behind a speed command, because these pumps re-learn their own flow range.

The connection is identical to the VSP

PinColourFunctioniSmart Module
1RedDigital Input 4Dry contact, if used
2BlackDigital Input 3Dry contact, if used
3WhiteDigital Input 2Dry contact, if used
4GreyDigital Input 1Dry contact, if used
5YellowDigital ground (COM)Common side of those contacts
6GreenRS485-APORT terminal A
7BrownRS485-BPORT terminal B
The seven-pin connector, from Moov's manual. Digital inputs are plain closures to the common on pin 5 — no supply voltage is involved.
The Moov seven-pin connector: four digital inputs and a common on pins 1 to 5, and the Modbus RS-485 pair on pins 6 and 7.
One connector, two ways in. Use the pair on pins 6 and 7 wherever you can.
InputColourEffect while closed to COM
Digital Input 1GreyPump forced to stop
Digital Input 2WhiteRun at 100%
Digital Input 3BlackRun at 80%
Digital Input 4RedRun at 40%
Each input is asserted by closing it to the common on pin 5. The capacities behind inputs 2, 3 and 4 can be changed in the pump's parameter settings.
Moov pin 6 (green, RS485-A) to PORT terminal A and pin 7 (brown, RS485-B) to PORT terminal B, with pins 1 to 5 cut back and the PORT's G terminal unused.
Two conductors end to end. Modbus is a two-wire pair here, so G stays empty.
The module's four dry contacts driving Moov digital inputs 1 to 4, all returning through the yellow common on pin 5.
Four contacts and one common return. Every dry output on the module is consumed.

What is different about the AI

  • Self-priming can be exited by hand at the pump, which helps during commissioning.
  • With it disabled, a manual self-prime can still be triggered at the pump if the basket has drained after a long idle period.
  • After a self-prime the pump redefines its adjustable flow range, so the meaning of a given speed request can shift.

When it does not respond

SymptomWhere to look first
Ignores commands for the first half hourSelf-priming still enabled.
Modbus commands ignored entirelyA digital input is closed to common.
No communicationSwap green and brown, then check the serial settings.
Same request gives a different flow than last monthA self-learning cycle has redefined the range. Expected behaviour on this range.