InverFlow pumps accept Modbus over RS-485 or four dry-contact digital inputs. Two things decide whether the install behaves: disabling self-priming, and understanding that the digital inputs outrank the bus.

Disable self-priming first

  • Disable the default self-priming function in parameter 6.
  • Parameter 7 sets the self-priming recheck time if you want to keep priming but shorten it.
  • The cycle can also be exited by hand at the pump, which is useful during commissioning but is not a substitute for turning it off.

Control priority

RS-485, the preferred route

Land the pump's RS485-A and RS485-B on a PORT. This is the option worth taking: one pair of conductors, full speed control rather than four fixed steps, and it leaves the module's dry contacts free for other equipment.

MadimackiSmart Module
RS485-APORT terminal A
RS485-BPORT terminal B

Digital inputs, the fallback

Where the bus is not available, four digital inputs give fixed speed steps. Each is driven from a dry contact on the module using COM and N.O so it rests open.

InputEffect when active
Digital input 1Pump forced to stop
Digital input 2Run at 100%
Digital input 3Run at 80%
Digital input 4Run at 40%
None activeReturns to its last known state and panel control
Default capacities. Madimack allows the percentages behind inputs 2, 3 and 4 to be changed in the parameter settings.

When it does not respond

SymptomWhere to look first
Runs at its own speed for the first half hourSelf-priming still enabled. Parameter 6.
Modbus commands ignoredA digital input is asserted. Check for the DI icon on the pump screen.
No communication at allSwap RS485-A and RS485-B, then check address and baud rate.
Panel will not respond eitherA digital input is active — the panel locks out by design.
Wrong speed on a digital inputThe default percentage behind that input was changed in the parameter settings.